Need a Lift Gate?

If you require a lift gate for delivery, click here to add our lift gate option to your order.

Single System - Glycol Makeup Package
Single System - Glycol Makeup Package

Single System - Glycol Makeup Package

The Wessels single system GMP is designed to automatically service one closed-loop system. This GMP-series is available with 50 or 100 gallon reservoir capacities and 1/3 and ½-HP pump pressurization control station with magnetic starter. The 1/3-HP is used for systems requiring up to 50-PSI metering pressure, and the ½-HP station is used for systems requiring up to 70 PSI.

*Drum Not Included. Purchase Drums Here.

Tank Volume: 50 GAL
Pump Capacity:: 1/3 HP
1 Week Lead Time.
Select your size to view its price!
Price
$5,236

Frequently Bought Together

FAST ORDER FULFILLMENT | NO MINIMUM ORDERS
Need help determining your required concentration?: Try our helpful glycol calculator tools!

Overview

The single GMP unit is designed to automatically supply a pressurized solution, such as glycol and water, to a closed loop heating, chilled water, snowmelt, radiant heating, sprinkler, or process control system to ensure minimum system pressure requirements are met. These systems are equipped with HOA controls, an adjustable pressure reducing valve (PRV), pressure gauge, and a low level alarm that cuts power to the pump and actuates an
audible and visual alarm when solution levels are too low.


Dimensions & Weights

  • Dimensions in Inches: 34 x 45 (50 Gallon) 34 x 68 (100 Gallon)
  • HP: 1/3, 1/2
  • Pressure Range (PSI): 10-70
  • Make-Up Capacity (GPM @ PSI): 1.8 @ 70
  • Approx. Shipping Weight (lbs):
    1/3 HP – 50 Gal: 134 lbs
    1/3 HP – 100 Gal: 140 lbs
    1/2 HP – 50 Gal: 138 lbs
    1/2 HP – 100 Gal: 144 lbs

Performance Specifications

  • Maximum Temperature: 160 F
  • Factory Discharge Pressure Setting: 12 PSIG
  • Maximum Discharge Pressure: 70 PSIG (Higher Discharge Pressures Available)
  • All electrical components are listed UL/CSA
  • Standard Starter Panel UL/CSA 60947-4-1
  • Optional NEMA 4X Panel UL/CSA LR19791
  • Available Options: High Level Alarm

Custom Mix Concentrations

Our heat transfer specialists can also custom mix concentrations to your specifications. Contact us to request a custom premix.

Bulk Propylene Glycol Available

We offer bulk tanker delivery and installation on 2,500 gallons or more. Contact us for a quote today.

Common Questions

What concentration of glycol do I need? What is the freeze point or burst point of propylene glycol?
How many gallons of glycol do I need to correct or balance my concentration?
How many containers do I need? What size is best?
See all frequently asked questions

You can find all of our most commonly asked questions on our FAQ Page - See all frequently asked questions